TIRA


Type: TCZ 4036 S (m) -2K
Walk-in Climate Simulation Chamber
Description:
 
System Structure:
 
The system consists of the following main components:
Walk-in, Insulated Chamber
Air Treatment Room
Machine Room with Humidification System and Control Cabinet
The insulated chamber serves as the test area and includes the air treatment room.
In the air treatment room, the air is conditioned (cooled/heated) and
dehumidified or humidified, and circulated by a fan.
A humidifier located in the machine room provides the steam required for
humidification.
The machine unit supplies the air treatment room with the necessary energy
through the refrigeration components (evaporator and dehumidifier).
The control cabinet located in the machine room houses all control and
regulation units as well as electrical components.
The control system ensures constant temperature regulation and stable
control behavior.
The control panel located on the left side wall of the climate chamber
allows for comprehensive operation.
Technical Data:
Performance Range for Temperature Testing:
Temperature Range -40...+140°C
Temperature Consistency, Inlet Air: (temporal) ≤ ± 1.0°C
without thermal test chamber load according to (DIN 50011 Τ13) EN 60068
Temperature Consistency, Inlet Air: (spatial) ≤ ± 1.5°C
without thermal test chamber load according to (DIN 50011 Τ13) EN 60068
Heating Rate approx. 2.0 K/min
without thermal test chamber load (according to DIN 50011 /
EN 60068) or test specimen in the temperature range of -30°C...+85°C
Heat Compensation approx. 20 kW in the temperature range from +80°C to -20°C
Performance Range for Climate Testing
Temperature Range +10...+95°C
Humidity Operating Range 10...approx. 95% r.H
without thermal test chamber load
Dew Point Temperature Range +5...+89°C
without thermal test chamber load
Humidity Deviation, Inlet Air: (temporal) ≤ ± 2.5% r.H
without thermal test chamber load according to (DIN 50011 Τ13) EN 60068
Accuracy Class 2 (measured in the center of the test chamber)
Humidity Deviation, Inlet Air: (spatial) ≤ ± 5.0% r.H
without thermal test chamber load according to (DIN 50011 Τ13) EN 60068
Accuracy Class 2 (measured in the center of the test chamber)
Performance Range for Climate Testing with Heat Compensation
Temperature Range +10...+95°C
Humidity Operating Range 10...approx. 70% r.H
with max. 20 kW heat compensation
Dimensions: Test Chamber (WxDxH) approx. 2510 x 5270 x 2760 mm
Dimensions: External Dimensions (WxDxH) approx. 2910 x 8740 x 3320 mm
Clear Door Passage Test Chamber Door (WxH) 2510 x 2760 mm with window 1000 x 1000 mm, heated
Design:
Air Flow: Inlet Air: Perforated sheet at the rear wall, in the ceiling area
Exhaust Air: Perforated sheet at the rear wall, in the floor area
Temperature Control:
Direct cooling through evaporation of
refrigerant in a finned heat exchanger:
Heating with electric resistance heater
Dehumidification:
Direct dehumidification through evaporation of
refrigerant in a heat exchanger
Interior Cladding: Stainless Steel
Exterior Cladding: Steel sheet, galvanized, plastic-coated
Floor Design: Stainless Steel, smooth finish
Floor Load Capacity 15000 N/m²
Wheel Load (Contact Area ≥4cm²) 1500 N/Wheel
Door: Double-leaf door, stainless steel, painted outside with
window (WxH) 1000x1000 mm
Test Chamber Lighting: 4 Spotlights at 500W each
Insulation Two-layer insulation, 80 mm PUR foam,
120mm mineral wool
Refrigeration Unit (2 pieces) Blitzer
Refrigerant, single-stage R449A
Refrigerant, single-stage R449A
Refrigeration Machine Oil SEZ 32
Steam Humidifier Steam Humidifier
Color Scheme:
Chamber RAL9010, white
Door RAL9010, white
Machine Unit RAL 7035, light gray
Control Cabinet RAL 7035, light gray
Weights:
Complete System
(includes machine set, control cabinet, and humidification system) approx. 7700 kg
Machine Set KB 2x 127 approx. 1200 kg
Control Cabinet approx. 280 kg
Humidification System approx. 115 kg
Connections:
Nominal Voltage 400 V +6%/-10% 3/PE 50Hz
Nominal Power 195 kW
Nominal Current 315 A
Fixed Connection
Site-specific Protection 400 A slow
Main Switch built into the control cabinet housing
Humidification Water according to installation plan
Water Supply and Drainage according to installation plan
Weight: 10495 kg
Condition: used
Scope of Delivery: (See Image)
(Changes and errors in the technical data are reserved!)
We would be happy to answer any further questions by phone.

Technical characteristic Value
Item ID 23513
Condition Used
Model TIRA Begehbare Klimazelle
Manufacturer TIRA
Weight 10500000 g
document.querySelector("form > input[data-mail='subject']").value = "Webshop - Frage zu Artikel - Artikel-ID: " + vueApp.$store.state.items[23513].variation.documents[0].data.item.id;

EU Responsible Person

TIRA GmbH
Eisfelder Strasse 23/25
96528 Schalkau Germany
info@tira-gmbh.de
+49 367 66280-0

Manufacturer details

TIRA
TIRA GmbH
Germany

Switch to environmentally friendly refrigerant

The following work can be performed on climate chambers. Please contact us if you are interested.

 

  • Extraction and proper disposal of the previous refrigerant
  • Replacement of necessary components, if unavoidable
  • Evacuate the circuit and refill it with R 452A, for example.
  • Checking / adjusting overheating in expansion valves
  • Leak test
  • Test run of the system

Climate test cabinets