Weiss Climate Test Chamber WKL 100/+10 +10...+150°C 100 Liters with Humidity


Item ID: 22929

Condition: Used

Stock: Only ${ $store.getters['22929/currentItemVariation'].stock.net } in stock

The item is already sold

* Excl. VAT excl. Shipping

Weiss Climate Test Chamber


Here we offer a Weiss Climate Test Chamber.
Weiss Climate Test Chamber WKL 100/+10
Air-cooled with humidity +10 to 180°C
General Data:
Climate Test Chamber WKL 100/+10
Test chamber volume approx. 100 liters
Weight 170 kg
Data for mechanical stress:
Climate Test Chamber WKL 100/+10
Maximum load of the test chamber floor 10 kg
per shelf 10 kg
Total load of the shelf supports 50 kg
Data for operation:
Climate Test Chamber WKL 100/+10
Test chamber lighting Halogen bulb 12V, 20W
Nominal voltage 1/N / PE AC 230 V ± 10 % 50 Hz
Nominal power 2.7 kW
Nominal current 11.7 A
Fuse on-site 16A slow
Protection class
Control cabinet and operating panel IP 54
Heat output air-cooled test chambers:
Max. heat output to the environment 1700 W
Noise measurement Climate Test Chamber WKL 100/+10
Sound pressure level measured at 2m distance from the front, 1m height and free field measurement
approx. 56 dB(A)
Key figures for temperature tests Climate Test Chamber WKL 100/+10
Temperature range +10 to +150°C
Temperature differences in steady state
Temperature fluctuation over time in the center of the usable space ± 0.3 to ± 1 K
Spatial temperature deviation ± 1 to ± 2 K
(corresponds to temperature gradient) 2 to 4
Rate of temperature change
Heating 1.5 K/min
Cooling 3 K/min
Heat compensation -
Key figures for climate tests Climate Test Chamber WKL 100/+10
Data for humidification system
Content of the storage tank approx. 13 l
Water quality demineralized
pH value 6 – 7
Conductivity max. 20 μs/cm
Water consumption at constant temperature +40 °C, 92 %r.H. 1.3 l 24/h
Temperature range +10 to +95 °C
Humidity range 10 to 98 %r.H.
Temperature and humidity differences (in steady state)
Temperature fluctuation over time in the center of the usable space ± 0.3 to ± 0.5 K
Spatial temperature deviation ± 0.5 to ± 1.5
(corresponds to temperature gradient) 1 to 3
Humidity fluctuation over time in the center of the usable space ± 3 to ± 5 %r.H.
Conduct NW 50 mm
Refrigerant: R404A
Type: WKL 100/+10
For you as a buyer, the following information for safety!
 
The following points will be carried out on our offered chambers in advance:
1. Function check and replacement of necessary components
2. New filling with legally compliant refrigerant
3. Leak test with certificate
4. After successful inspection, the chambers will undergo a test run monitored with calibrated devices.
Condition: used
Scope of delivery: (See image)
(Changes and errors in the technical data, specifications are reserved!)
We would be happy to answer any further questions by phone.

Technical characteristic Value
Item ID 22929
Condition Used
Model Weiss Laborprüfschrank
Manufacturer Weiss
Weight 200000 g
document.querySelector("form > input[data-mail='subject']").value = "Webshop - Frage zu Artikel - Artikel-ID: " + vueApp.$store.state.items[22929].variation.documents[0].data.item.id;

EU Responsible Person

Weiss Technik GmbH
Greizer Straße 41-49
35447 Reiskirchen Germany
info@weiss-technik.com
+49 6408 84-0

Manufacturer details

Weiss
Weiss Technik GmbH
Germany

Switch to environmentally friendly refrigerant

The following work can be performed on climate chambers. Please contact us if you are interested.

 

  • Extraction and proper disposal of the previous refrigerant
  • Replacement of necessary components, if unavoidable
  • Evacuate the circuit and refill it with R 452A, for example.
  • Checking / adjusting overheating in expansion valves
  • Leak test
  • Test run of the system