Weiss Climate Cabinet WK 14'/20-80 MCS -40°C to +80°C


Item ID: 13806

Condition: Used

Stock: Only ${ $store.getters['13806/currentItemVariation'].stock.net } in stock

The item is already sold

* Excl. VAT excl. Shipping

White


Type: WK 14'/20-80 MCS
Climate Chamber
Test chamber volume: approx. 10m3
Weight of test chamber: 4600 kg
Cooling unit: water-cooled
Data for mechanical stress
maximum load (evenly distributed over the area)
of the test chamber floor: 50,000 N/m2
Floor load capacity: max. 400kg/0.0064m2 (4 feet (80x80 mm))
per rail 50 kg
Data for operation
Test chamber lighting: 6 x LED ceiling light 24V1.1A Pommier
Interference emission; immunity: standards met conformity declaration
Nominal voltage: 3/N/PE AC 400V ± 10% 50Hz
Nominal power: 46 kW
Nominal current: 71 A
Customer-side fuse: 80 A
Protection class of control cabinet and operating panel: IP 54
max. heat output of the test chamber to the environment: 3.5 kW
Noise measurement
Sound pressure level approx.: < 66 dB(A)
Data for compressed air
permissible pressure range: 6 to 12 bar g
Compressed air consumption: approx. 2 to 10 m³/h
Temperature range of customer-side compressed air: +2 to +50 °C
Compressed air connection: quick coupling self-closing DN 7.2
Compressed air quality according to ISO 8573-1
Solid contamination according to class 2: max. particle size 1 μm
Moisture content (vapor): according to application
Total oil content (liquid and gaseous): < 0.01 mg/m3
Data for temperature tests
Temperature range: -40°C to +80°C
Temperature change rate -20°C to +80°C (with test specimen 2600 kg)
Heating: 0.5 K/min
Cooling: 0.5 K/min
max. heat compensation at +45°C: 20000 W
max. heat compensation at +80°C: 10000 W
Data for climate tests
Data for humidification system
Water quality: demineralized
pH value: 6 to 7
Conductivity: 5 to 20 μS/cm
Water consumption: 10 l/h
Temperature range: +10 to +80°C
Humidity range: 15 to 80 %r.H.
Humidity range
with heat compensation 5000 W: 10 to 70 %r.H.
Dew point range: +7 to +74 °C
Humidity deviation over time
in the center of the usable space: ± 5.0 %r.H.
Data for cooling water
General data
required water pressure: 2.5 to 6 bar
Pressure difference in the cooling water circuit: > 2 bar
Inlet temperature: 12 °C to 20 °C
pH value: 7.5 to 9
Quality: free of dirt, as colorless and clear as possible
(max. size of dirt particles 100 μm)
Total hardness: max. 8°dH (approx. 80 mg CaO/l)
Electrical conductivity: < 500 μS/cm (reference temperature 20 °C)
Chloride: < 10 g/m3
Sulfate: < 100 g/m3
Hydrogencarbonate: < 300 g/m3
Ratio of sulfate / hydrogencarbonate: < 1
Nitrate: < 100 g/m3
Dissolved iron: < 0.2 g/m3
Free aggressive carbonic acid: < 20 g/m3
Cooling water inlet temperature: +20 °C
Cooling water outlet temperature: +25 °C
Cooling water connection: R 1”
Cooling water consumption at full load with:
Temperature difference Δt = 5K: max. 6.2 m³/h
Click here to download the technical drawing
Year of construction: 2013
The climate chamber has only a few operating hours, therefore in like-new condition.
Condition: used
Scope of delivery: (See image)
(Changes and errors in the technical data are reserved!)
We would be happy to answer any further questions by phone.

Technical characteristic Value
Item ID 13806
Condition Used
Model WK 14'/20-80 MCS / 2013
Manufacturer Weiss
Weight 4600000 g
document.querySelector("form > input[data-mail='subject']").value = "Webshop - Frage zu Artikel - Artikel-ID: " + vueApp.$store.state.items[13806].variation.documents[0].data.item.id;

EU Responsible Person

Weiss Technik GmbH
Greizer Straße 41-49
35447 Reiskirchen Germany
info@weiss-technik.com
+49 6408 84-0

Manufacturer details

Weiss
Weiss Technik GmbH
Germany

Switch to environmentally friendly refrigerant

The following work can be performed on climate chambers. Please contact us if you are interested.

 

  • Extraction and proper disposal of the previous refrigerant
  • Replacement of necessary components, if unavoidable
  • Evacuate the circuit and refill it with R 452A, for example.
  • Checking / adjusting overheating in expansion valves
  • Leak test
  • Test run of the system

Climate test cabinets

Show all