Heraeus Vötsch Temperature Testing Chamber VTV 7057-5/S -70°C to +180°C with Humidity!
Item ID: 19503
Condition: Used
Stock: Only ${ $store.getters['19503/currentItemVariation'].stock.net } in stock
PAYMENT METHODS:
²
* Excl. VAT excl. Shipping
Heraeus Vötsch Temperature Test Chamber
Here we offer you a Heraeus Vötsch temperature test chamber.
Heraeus Vötsch temperature test chamber with chamber pass-through
for shakers for vibration testing
Control panel touch screen with Simcon/32
Temperature range -70°C to +180°C
Humidity range: Relative humidity 5.0-98% rF
Temperature deviation over time ± 1 K
Temperature change rate
Heating in the range of -70°C to +180°C approx. 7 K/min.
Cooling in the range of +180°C to -60°C approx. 5 K/min.
Case dimensions:
approx. Height 2000 mm Width 1300 mm Depth 2600 mm
Test chamber dimensions:
approx. Height 870 mm Width 825 mm Depth 800 mm
Window 300x500 mm
2x side pass-through NW 80 cm
1x side pass-through NW 50 cm
Test chamber volume 330 liters
Nominal voltage: 3/N/PE AC 400V ± 10% 50Hz
Nominal power: 20 kW Nominal current: 38 A
Fuse, site-specific: 63 A slow-blow
Weight approx. 650 kg
Refrigerant: R-507 and R-23
For you as a buyer, the following information for safety!
The following points will be carried out on our offered chambers in advance:
1. Function check and replacement of necessary components
2. New filling with legally compliant refrigerant
3. Leak test with certificate
4. After successful inspection, the chambers will undergo a test run monitored with calibrated devices.
Type: VTV 7057-5/S
Condition: used
Scope of delivery: (See image)
(Changes and errors in the technical data are reserved!)
We are happy to answer any further questions by phone.
Switch to environmentally friendly refrigerant
The following work can be performed on climate chambers. Please contact us if you are interested.
- Extraction and proper disposal of the previous refrigerant
- Replacement of necessary components, if unavoidable
- Evacuate the circuit and refill it with R 452A, for example.
- Checking / adjusting overheating in expansion valves
- Leak test
- Test run of the system